Configuration
Setting values
38 / 216
Siemens
Building Technologies
5.5
Remote setpoint adjuster, absolute
The absolute remote setpoint acts on setpoints of the universal controller of the
RMS705B.
Setpoint sources BSG21.1 (0...1000 ) and BSG61 (0...10 V) are ideal for room
unit QAA25 (5...35 °C).
The absolute remote setpoint acts on both Comfort and Economy setpoints.
5.5.1
Activate function
The function is activated by setting the identifier of an input as a remote setpoint. At
the same time, specify the controller (1...3) the remote setpoint should act on.
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
...X...
5.5.2
Type and measuring range
You can select if the remote setpoint is to be an active (DC 0...10 V) or passive
signal (0...1000 Ω).
In addition, you can set the input signal's range:
"Value high": Value at DC 10 V or at 1000 Ω
"Value low": Value at DC 0 V or at 0 Ω
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line
Type
Value low
Value high
Switching and monitoring device RMS705B
Inputs
Adjustable values / Comment
Activate the function by assigning the following value to
the input:
[Controller 1] rem setp adj (Rem-w1),
[Controller 2] rem setp adj (Rem-w2) or
[Controller 3] rem setp adj (Rem-w3).
Range
0...10 V, Ohm
Depending on selected type
Depending on selected type
Factory setting
Ohm
Type-dependent
Type-dependent
CE1P3124en