Modulating load input with
switching command outputs
(Example 1)
Configuration
Siemens
Building Technologies
Application examples
Load input,
Number of
start condition
stages or
aggregates
A+B+C+D
a
Description:
- Several recirdulated air heaters with different capacities are controlled to room temperature.
- Rated outputs for the 4 aggregates controlled digitally by the flexible step switch: Aggregate A = 1
kW, Aggregate B = 1 kW, Aggregate C = 2 kW, Aggregate D = 3 kW.
- The total output at X
= 100 % is 7 kW.
P
Plant diagram
1 KW
1 KW
DI
AI
DO
AO
Configuration diagram
Rotary
step switch 1
X
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1...2 >
Operating line
Type
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
Output A
Output B
Output C
Output D
Switching and monitoring device RMS705B
Aggregates
Output configuration
A
B
1
4
Start
d
d
3 KW
2 KW
4
3
2
1
T
C D
C
D
Setting
Flexible
Range
0.1...999.9
0.1...999.9
0.1...999.9
0.1...999.9
Run priority
C
D
changeover
d
d
No
Function diagram
A
B
C
D
0 %
X
P
B
D
C
B
0 %
X
P
Setting
1.0
1.0
2.0
3.0
CE1P3124en
01.04.2010
100 %
A
B
C
100 %
91 / 216