Enthalpy Calculator - Siemens Synco 700 RMZ785 Basic Documentation

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Purpose
Function range A
Function range B
Definition of short names
Range
A
B
Siemens
Building Technologies
9.2

Enthalpy calculator

The function block calculates the following based on inputs temperature and
relative humidity:
Function range A (inputs Temp A and RelHu A):
 Enthalpy A
 Absolute humidity A
 Dew point temperature
 Wet bulb temperature
Function range B (inputs Temp B and Rel Hu B):
 Enthalpy B
 Absolute humidity B
 Enthalpy difference (Enthalpy A Minus Enthalpy B)
The results of the calculations are provided as DC 0...10 V signals or as internal,
analog signal.
Inputs
Temp A
Temperature input A
RelHu A
Relative humidity input A
Temp B
Temperature input B
RelHu B
Relative humidity input B
Switching and monitoring device RMS705B
Signal converter
Outputs
Enth A
Enthalpy A
Abso Hu A
Absolute humidity A
Dew Pnt
Dew point temperature
Wet Blb
Wet bulb temperature
Enth B
Enthalpy B
Abso Hu B
Absolute humidity B
Enth Diff
Enthalpy difference A-B
131 / 216
CE1P3124en
01.04.2010