Siemens Synco 700 RMZ785 Basic Documentation page 134

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Example for signal
doubling
Function diagrams
Siemens
Building Technologies
Signal doubling with sequential control of the outputs, i.e. after output A is
controlled, output B is controlled.
Input signal A limitation:
Output A corresponds to: "Positioning signal min A" (YminA) to "Positioning signal
max A" (YmaxA).
10 V
max A
min A
0 V
0 %
Value low A
Input signal B limitation
Output B corresponds to: "Positioning signal min B" (YminB) to "Positioning signal
max B" (YmaxB).
10 V
maxB
minB
0 %
0 V
Switching and monitoring device RMS705B
Signal converter
Value low B
135 / 216
CE1P3124en
01.04.2010