Assigning An Ip Address - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4. Select the drive, and if necessary assign an IP address and device name, see also the
Chapters "Assigning an IP address (Page 143)" and "Assigning PROFINET device
names (Page 145)".
Figure 4-48
The drive is displayed with the device name (in this case, drive_1) and the IP address.
If you cannot assign an IP address and device name, you may have to check the IP
address of your PG/PC. This must also lie in the same address range as the address of
the drive, see also Chapter "Setting the PG/ PC interface (Page 147)".
Result
You have found the device in the PROFINET subnet and assigned an IP address and a
device name.
Now establish an online connection.
4.5.3.3

Assigning an IP address

Adapting the IP address in the drive
Before you can go online on a drive via PROFINET, you must assign the PROFINET
interface of the drive a suitable IP address.
● When supplied, the PROFINET interface of the drive has no IP address.
● If a cyclic connection already exists from SINAMICS to the controller, it is no longer
possible to assign an IP address.
The PROFINET interface has already been assigned an IP address and subnet mask in the
project:
● IP address: 192.168.0.1
● Subnet mask: 255.255.255.0
The IP address and subnet mask lie in the subnet of an S71500 control, which simplifies
networking the control system and drive.
Requirement
An online connection to the drive exists, and you have made a search for the drives under
Online access in the appropriate interface with "Update accessible devices".
The device is displayed.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
PROFINET with IP address
4.5 Establishing an online connection to the drive unit
Commissioning
143