Siemens SINAMICS S120 Commissioning Manual page 344

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnostics
5.3 Diagnostics via Startdrive
Trigger condition: Trigger on alarm
1. In order to record a time period before the trigger event, enter a value greater than 0 in
the input field for the pre-trigger.
2. Enter the recording time under "Recording duration". The maximum possible recording
duration is displayed to the right.
Should you wish to set the maximum recording time, activate the option "Use max.
recording duration".
3. Enter a recording cycle under "Cycle" The possible cycle settings depend on the number
of signals.
Trigger condition: Trigger on fault
1. In order to record a time period before the trigger event, enter a value greater than 0 in
the input field for the pre-trigger.
2. Enter the recording time under "Recording duration". The maximum possible recording
duration is displayed to the right.
Should you wish to set the maximum recording time, activate the option "Use max.
recording duration".
3. Enter a recording cycle under "Cycle" The possible cycle settings depend on the number
of signals.
Additional information
Additional information on handling the trace function and the configuration and evaluation of
the trace is provided in the Startdrive online help.
344
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1