Commissioning
4.7 Basic parameterization of the drive objects
After performing the basic parameterization and subsequent download, the "Stationary
measurement" measurement type is active as the "Calculation of motor/control parameters"
has already been performed.
1. Click the "1" icon in the "Infeed " area to switch on the infeed.
2. To set the drive enable signals, click "Set" in the "Drive enables" area.
3. Click the "1" icon in the "Switch on" area to switch on the motor.
4. Click "Start" in the "Measurement" area to start the measurement.
A status display at the center of the screen form shows how the measurement is
progressing (r0047).
The measurement ends automatically, and the message appears that the drive is in the
switch-on inhibited state.
After the measurement, the new parameter values are displayed in the results table. You
can view and check the new values.
5. Check the values that have been determined to ensure that they are plausible.
6. You can accept the values if they are OK. To do this, click "Accept values".