Siemens SINAMICS S120 Commissioning Manual page 210

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
4.9 Commissioning a drive
Calling the control panel
1. In the project tree, select the "Drive unit_x > Drive axis_x > Commissioning" menu.
2. In the commissioning secondary navigation, select the "Control panel" menu.
When an online connection has been established, the bar in the header area is shown in
color. The control elements are grayed-out apart from the "Activate" button. The
remaining control elements become active after you have activated the control panel and
set the enables.
Figure 4-89
Activating the control panel
When you activate the control panel, you assume master control of the drive. The control
panel can always only be activated for one drive.
To activate the control panel, proceed as follows:
1. Click "Activate" at "Master control".
The "Activate master control" message window opens.
2. Read the warning carefully and check the value for the monitoring time.
The monitoring time specifies the time during which the connection from the PG/PC to the
drive is monitored. The minimum value is 1000 ms.
3. Click "Continue" to confirm the monitoring time.
The message window closes. The control panel is then active.
210
Control panel
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1