Control Units; Led States Of A Cu320-2 - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.2.1

Control Units

5.2.1.1

LED states of a CU320-2

The various states of the CU320-2 PN Control Unit when powering up and in operation are
displayed using LEDs on the Control Unit. The duration of the individual statuses varies.
Table 5- 2
LED
RDY
COM
OPT
● If an error occurs, the power-up procedure is terminated and the cause is indicated
accordingly via the LEDs.
● Once the unit has successfully powered up, all the LEDs are switched off briefly.
● Once the unit has powered up, the LEDs are controlled via the loaded software.
Control Unit 320-2 when the powering up
Table 5- 3
Control Unit CU320-2 – description of the LEDs during ramp-up
LED
Color
RDY
Red
COM
Orange
OPT
Orange
RDY
Red
COM
Red
RDY
Red
COM
Red
RDY
Red
COM
Orange
RDY
Red
RDY
Red
COM
Red
COM
Red
RDY
Red
COM
Red
RDY
Orange
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
LEDs
Function
Ready
PROFIdrive cyclic operation via PROFINET (PN)
OPTION
Display
State, description, cause
Steady light
Hardware reset
Steady light
BIOS loaded
Flashing light 2 Hz
BIOS error: "An error occurred while loading the BIOS".
Steady light
Steady light
Loading firmware: RDY LED lights up red, COM LED flashes
orange without fixed frequency.
Flashing light
Steady light
Firmware has been loaded.
Flashing light 2 Hz
File error:
Steady light
Firmware has been checked. No CRC error detected.
Flashing light 0.5 Hz
Firmware has been checked. CRC error detected.
Steady light
Initializing firmware
Memory card not available or faulty.
Software on memory card not available or faulty.
Diagnostics
5.2 Diagnostics using LEDs