Commissioning
4.10 Safety Integrated commissioning
Settings
1. Call the "SLS" safety functions.
A screen form with this name opens.
Figure 4-104 Example: SLS-PROFIsafe with onboard terminals
2. Click the
The "Control" screen form opens. The way the screen form is displayed depends on the
basic settings of the Safety Integrated function SLS.
In this screen form, configure the controls via the fail-safe inputs and outputs and/or
PROFIsafe (see Chapter "Control (Page 281)").
3. Call the "SLS" safety function again.
4. Enter a delay time in field "Delay Time Selection SLS >> SLS active" (P9551).
5. Enter a suitable value for level 1 of the speed limit (p9531[0]).
6. Select a suitable stop response for level 1 from the drop-down list (p9563[0]).
7. Click the
Screen form "SS2" opens:
Set the desired motor deceleration here (see Chapter "SS2 (extended functions)
(Page 241)")
8. If you want to additionally configure levels 2, 3, and/or 4 for the speed limit, repeat steps 5
to 7 for each level.
9. In field "Setpoint velocity limitation SLS level" (p9533) enter a weighting factor to
determine the setpoint limit from the selected actual speed limit in percent.
10.If you want to use a PROFIsafe override for level 1 of the speed limit, choose item
"Enabled" from the "PROFIsafe-Override" drop-down list (p9501.24).
254
button (Select SLS) to configure activation of the "SLS" function.
icon to open the configuration for level 1.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1