Commissioning
4.4 Creating a project offline in Startdrive
Operation of several VSMs per Line Module
You can add a total of up to three VSMs to each Line Module using drag and drop.
Note
Activating the "Line transformer" function module
If you operate several VSMs on one Line Module, you must activate the "Line transformer"
function module in the basic parameterization of the Line Module.
Note
Deleting additional Voltage Sensing Modules
If you delete additional VSMs, you must deactivate the "Line transformer" function module in
the basic parameterization. Otherwise the computing power of the Control Unit may be
adversely affected.
136
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1