3.8 Protection against electric shock

Ensuring protection against electric shocks when using DB1 variable
frequency drives, as per IEC/EN 61800-5-1
Manufacturer's declaration for the initial verification as per
IEC/HD 60364-6
(DIN VDE 0100-600 (VDE 0100-600)) and for periodic testing as per
EN 50110-1 (DIN VDE 0105-100 (VDE 0105-100))
Fault protection as per IEC/HD 60364-4-41 (DIN VDE 0100-410 (VDE 0100-410))
for the circuit on the output site of the aforementioned equipment is ensured
based on the following requirements:
The installation instructions in this documentation have been observed.
The applicable standards in the IEC/HD 60364 (DIN VDE 0100
(VDE 0100) series have been observed.
The continuity of all associated protective conductors and equipotential
bonding conductors, including the corresponding connection points, has
been ensured.
Provided that the above requirements are met, the aforementioned equip-
ment meets the requirements in IEC/HD 60364-4-41 (DIN VDE 0100-410
(VDE 0100-410):2007-06, section 411.3.2.5) when using the "automatic
power supply shutdown" protective measure.
The note is based on the following information:
In the event of a short-circuit with negligible impedance to a protective con-
ductor or to ground, the aforementioned equipment reduces the output volt-
age within the times as per Table 41.1 or otherwise within 5 seconds –
whichever applies – in accordance with IEC/HD 60364-41(DIN VDE 0100-410;
VDE 0100-410):2007-06).