5.4.5 Replacing a Fire Alarm Bell

Prerequisites
Impact on the System
None
Preparations
Tools: needle-nose pliers, insulation tape, protective gloves, step ladder
Materials: crimp terminals, spare fire alarm bell
Documents required: fire extinguishing device layout diagram
Skill requirement: fire extinguishing engineer
Procedure
Step 1 Push the fire alarm bell out of the base, as shown in
Figure 5-45 Removing a fire alarm bell
Step 2 Cut off the power cable of the fire alarm bell, as shown in
Issue 01 (2016-01-10)
A fire alarm bell is faulty.
A spare fire alarm bell of the same model is available and functional.
For the diagram and table, see the initial configuration guide.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
Figure
5-45.
Figure
5-46.
128