8.5 Commissioning Fire Extinguishing Devices
8.5.1 Commissioning Fire Extinguishing Devices (Standard)
8.5.1.1 Commissioning the Fire Alarm Control Panel (standard)
Prerequisites
Initial configuration parameters have been set for the fire alarm control panel before delivery
and do not need to be set onsite.
Preparations
Tools: none
Documents required: power supply and distribution system diagram, documents delivered
with the agent releasing control panel, fire extinguishing system conceptual diagram
(standard), fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Procedure
Step 1 Switch on the input power circuit breaker of the fire alarm control panel for the protected area
by referring to the power supply and distribution system diagram.
Step 2 Switch on the active and standby power supply to power on the fire alarm control panel.