Item
35 kW
air-cooled
precision
air
conditioner
Issue 01 (2016-01-10)
Method
Expected Result
Measure the phase
Each phase
currents when the
current is no less
humidifier is
than 1.2 A (1/3 of
working.
the rated current).
Start the air
Water can be
conditioner, choose
smoothly taken in.
Maint >
Diagnostic
Mode > Enter
from the main
screen, set the
humidifier input to
50%, and check
whether water can
be smoothly taken
in.
(Following the
Water drainage is
preceding step) Set
normal.
the humidifier
input to 0%, and
press the manual
drainage button on
the side of the
electric control box
to check whether
water drainage is
normal. After the
check is complete,
set the manual
drainage button on
the side of the
electric control box
to normal
humidification.
Start the air
The electric heater
conditioner, choose
generates heat.
Maint >
Diagnostic
Mode > Enter
from the main
screen, and set
Electric heater to
On. Check whether
the electric heater
generates heat.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
Replace the humidifier
cylinder by following
instructions in the air
conditioner user manual.
Check that the water inlet
sluice is open.
Disconnect the humidifier
water injection hose and clear
the blockage in the hose.
1. Disconnect the water hose,
and hammer it with a rubber
mallet to shake off foreign
matters.
2. Remove the water pump and
clean up foreign matters in it.
3. If there are too many foreign
matters and they cannot be
cleaned up, replace the water
pump by following
instructions in the air
conditioner user manual.
Replace the electric heater by
following instructions in the air
conditioner user manual.