IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Fault
Category

4.18 PDU8000 MDU Alarms

Fault
Category
PDU8000
MDU
alarms
Issue 01 (2016-01-10)
Alarm
Symptom
Severity
The SPD circuit
breaker is off.
Alarm
Symptom
Severity
Major
The user interface
does not display
branch currents.
Major
The user interface
fails to display the
circuit breaker
status.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
A false alarm is
Switch on the SPD
generated
circuit breaker.
(normally
closed contact).
Possible
Troubleshooting
Cause
The monitoring
Check that cables are
board
properly connected.
communication
s cable or the
secondary cable
to the
corresponding
branch current
transformer is
not properly
connected.
The monitoring
If the monitoring board
board or current
or current transformer
transformer is
is faulty, replace the
faulty.
faulty monitoring board
or current transformer.
The
Check that the Boolean
communication
value collection module
s cable of the
is properly connected to
Boolean value
the branch Boolean
value signal cable.
collection
module or the
corresponding
branch Boolean
value signal
cable is not
properly
connected.
The Boolean
Check the Boolean
value collection
value collection module
module or
and auxiliary switch
auxiliary switch
contact. If the collection
contact is
module or auxiliary
faulty.
contact is faulty,
replace it.
4 Alarms and Faults
61