IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Item
Thermal
insulation
foam for
the
humidifier/
condensate
drainpipe
If a cooling component needs to be powered off for maintenance, take measures to prevent
device overheating before powering off the component.
Issue 01 (2016-01-10)
Method
Expected
Result
Check electric
The electric
heaters.
heaters and
switches are
secure.
The electric
heater surface
is not
corroded.
Check the
Check that T/H
temperature-humid
sensors in the
ity sensor.
air conditioner
and aisles are
securely
installed.
Check the water
The water
sensor.
sensor is
secure, and the
two downward
metal
conductive
plates do not
touch with
each other and
are free from
corrosion.
Check whether the
The thermal
thermal insulation
insulation
layers are in good
layers are in
condition without
good condition
condensation.
and free from
condensation.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
Secure the electric heaters and
switches.
Replace the electric heater by
following instructions in the air
conditioner user manual.
Secure the T/H sensor.
Replace the water sensor by
following instructions in the air
conditioner user manual.
If there is condensation under a
pipe, replace the thermal insulation
layer by following instructions in
5.2.6 Replacing a Thermal
Insulation
Layer.