Monitoring System - Huawei IDS1000-A Maintenance Manual

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide

3.2.3 Monitoring System

Table 3-4 Monthly maintenance checklist for the monitoring system
Item
Event and
operation
logs in the
RH2288 V2
server.
ECC500
collector
VCN500
Access
control
system
Hydrogen
detection
system
Issue 01 (2016-01-10)
Method
Expected
Result
Choose System
Normal system
Event Log in the
events are
navigation tree.
displayed.
Check the
The running
indicators of the
indicator is
ECC500 main
steady on.
control module.
Check the
The VCN500
VCN500 indicator.
indicator is
steady green.
Swipe a card to
When an
open the door.
access card is
swiped, the
card reader
indicator
becomes red
for 3s (you
will bear a
beep) and then
returns to
steady blue.
Press the exit
The door can
button and open
be opened.
the door.
Check the
The normal
hydrogen density
value is 0% or
that is displayed.
1%.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
See the documents delivered with
the RH2288 V2 server.
If the running indicator is
blinking quickly, check the
power supply or the
communications cable between
the ECC500 and the host.
If the alarm indicator is on, view
and handle the alarms.
See the documents delivered with
the VCN500.
Swipe another access card and
observe the door status:
If the door can be opened by
another access card, the original
access card is damaged. Prepare
a new access card and assign
permission to the card.
If the door cannot be opened,
replace by following instructions
in
5.3.13.1 Replacing a Card
Reader.
1. Check whether the cable to the
exit button is properly
connected.
2. If the fault persists, replace by
following instructions in
Replacing an Exit
Button.
If the density is abnormal, contact
Huawei technical support.
5.3.13.2
16

Advertisement