M Precautions; Issue - Huawei IDS1000-A Maintenance Manual

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Power Supply and Distribution System
During battery O&M, observe the following:

Issue 01 (2016-01-10)

Before replacing a component, ensure that the component and its battery are powered
off.
When operating power distribution equipment, follow the local regulations and rules.
When performing high-voltage and AC operations, use dedicated tools and wear
protection equipment.
Before entering the power supply area, check the hydrogen density and take protective
measures.
Do not install or remove power cables for a device which is powered on. Transient
contact between the core of the power cable and the conductor may generate electric arcs
or sparks, which may cause fire or hurt human eyes.
Before removing component cables, mark the cables with their corresponding port
numbers for later connection.
Before connecting a power cable, check that the label on the power cable is correct.
Assess impact on the system before switching off the general circuit breaker or cutting
off the cooling system during parts replacement.
For the detailed power control relationships between devices, see the power distribution
system diagram.
Insulate tools before battery O&M.
Assign only professional engineers to perform the O&M.
Do not use any organic solvent to clean batteries.
Do not remove the safety valve or fill anything into batteries.
Do not smoke or use fire around batteries.
Do not place tools on bare batteries terminals.
Do not short-circuit the terminals of lead-acid batteries; otherwise, a fire may occur.
Do not maintain batteries online. Replace a battery if it is faulty.
Charge the battery within 24 hours after battery discharge; otherwise, the battery
capacity will be affected.
Do not open lead-acid batteries as electrolyte leakage may cause bodily injuries. If you
contact the electrolyte accidentally, immediately clean your skin with water and seek
medical advice from a doctor.