Huawei IDS1000-A Maintenance Manual page 41

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Item
Access
control
system
Issue 01 (2016-01-10)
Method
Expected
Result
(Optional) Check
the magnetic lock
indicator.
(Optional) Check
The indicator
the electronic lock
turns red when
indicator.
the container
door is opened.
The indicator
turns green when
the container
door is closed.
Press down the
The container
button after
door can be
removing the glass
opened.
cover of the
emergency door
release button.
Press the exit
The door can be
button and open
opened.
the door.
Swipe a card to
When an access
open the door.
card is swiped,
the card reader
indicator
becomes red for
3s (you will bear
a beep) and then
returns to steady
blue.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
The indicator
If the indicator status is incorrect,
turns red
replace by following instructions
when the
in
5.3.13.3 Replacing a Magnetic
container
Lock.
door is
opened.
The indicator
turns green
when the
container
door is
closed.
If the indicator status is incorrect,
replace by following instructions
in
5.3.13.4 Replacing the
Electronic
If the container door cannot be
opened, replace by following
instructions in
an Emergency Door Release
Button.
1. Check whether the cable to the
exit button is properly
connected.
2. If the fault persists, replace by
following instructions in
5.3.13.2 Replacing an Exit
Button.
Swipe another access card and
observe the door status:
If the door can be opened by
another access card, the
original access card is
damaged. Prepare a new
access card and assign
permission to the card.
If the door cannot be opened,
replace by following
instructions in
Replacing a Card
3 Maintenance
Lock.
5.3.13.5 Replacing
5.3.13.1
Reader.
33