3.2.4 Fire Extinguishing System (Standard)

Table 3-5 Monthly maintenance checklist for the fire extinguishing system
Item
Fire control
panel
Fire
extinguisher
Lights
Issue 01 (2016-01-10)
Method
Expected
Result
Check indicators
The power
on the fire control
indicator is on,
panel.
and the alarm
indicator is
off.
Check the fire
The
cylinder, solenoid
components
driver, pipes, and
are not
nozzles.
misshapen due
to collision
and have no
mechanical
damage.
The
components
have no rust
on the exterior,
and the coating
is intact.
The protective
cover, lead
seal, and
safety signs on
hand-operated
devices are
intact.
Read the pressure
The pressure
shown on the
pointer is in
pressure gauge.
the green zone.
Press TEST on the
The
emergency light
emergency
panel.
light is on
when you tap
TEST.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
Replace a faulty component by
following instructions in Fire
Alarm Controller/Fire Control
Panel User Manual or
5.4.9
Replacing a Fire Control
Replace the fire cylinder by
following instructions in
Replacing a Fire
Cylinder. For
details, about how to replace other
components, contact Huawei
technical support.
Repair the paint.
Replace a faulty component.
Contact the local maintenance
engineers for prompt pressure
increase.
1. Check and reconnect power
cables to the emergency lights.
2. If the fault persists, replace by
following instructions
Replacing an Emergency
Panel.
5.4.8
in5.4.10
Light.