Emergency Operations For Overtemperature; Emergency Operations For The Management System Communication Failure - Huawei IDS1000-A Maintenance Manual

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.

6.5 Emergency Operations for Overtemperature

Prerequisites
The IDS1000 is experiencing overtemperature or an overtemperature alarm is generated.
Procedure
Step 1 Locate the high-temperature area.
Step 2 Measure the actual ambient temperature using a thermometer.
Step 3 Check whether the actual temperature exceeds the designed normal range.
Step 4 Lower the temperature in the area.
Step 5 For details, see
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.6 Emergency Operations for the Management System
Communication Failure
Prerequisites
The management system communication is interrupted.
Before the management system communication is restored, the management system cannot
perform real-time monitoring for the IDS1000 data center. Add people to perform preventive
maintenance inspection in related areas.
Issue 01 (2016-01-10)
If no, check whether the T/H sensor is faulty, and replace by following instructions in
Replacing a T/H Sensor
If yes, go to
Step
4.
4.9 Temperature
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
if it is faulty.
Alarms.
6 Emergency Operations
5.3.1
154