Huawei IDS1000-A Maintenance Manual page 79

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Fault
Category
Issue 01 (2016-01-10)
Alarm
Symptom
Severity
Major
The compressor
generates a loud
noise.
Major
An indoor fan does
not work.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The sheet metal
Remove the sheet metal
for securing the
and check whether the
abnormality disappears.
compressor
during
transportation
is not removed.
The compressor
Troubleshoot by
starts and stops
following instructions
at short
in Comp HP switch,
intervals.
and check whether the
abnormality disappears.
The compressor
Contact Huawei
suffers from
technical support.
liquid strike.
A fan alarm is
Check whether an
generated.
alarm is generated. If
yes, handle the alarm
by referring to the
alarm reference list.
The fan does
Choose Running >
not need to
Status on the controller
work.
home screen and check
the indoor fan control
status. If the control
status is 0%, the fan
does not need to work,
and there is no fault. If
the control status is
greater than 0%, the fan
is faulty and needs to be
rectified.
The switch of
Turn on the switch, and
the indoor fan
check whether the
abnormality disappears.
is not turned
on.
4 Alarms and Faults
71