Huawei IDS1000-A Maintenance Manual page 94

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Preparations
Tool: protective gloves
Material: spare air filters
Documents required: none
Skill requirement: cooling engineer
Procedure
Step 1 Open the rear door, and rotate the fixing cards on the two sides of the gauze, as shown by 1 in
Figure
Step 2 Pull out the air filter, as shown by 2 in
Figure 5-9 Removing the air filter
Step 3 Remove air filters at the middle and bottom in the same way.
Step 4 Install new air filters.
Issue 01 (2016-01-10)
5-9.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
5-9.
5 Parts Replacement
86