IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide

4.20 UPS5000-E Alarms

Fault
Category
UPS5000-
E alarms
Issue 01 (2016-01-10)
Alarm
Symptom
Severity
Major
The rectifier cannot
work, and the bus
voltage is not
boosted.
Major
The buzzer buzzes,
the Fault indicator is
on, the inverter is
faulty, and the UPS
transfers to bypass
mode.
Major
When the mains is
normal, the UPS
works in bypass
mode and does not
transfer to inverter
mode.
For other UPS5000-E alarms, see documents delivered with the product.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The mains
Check whether the
voltage exceeds
mains voltage exceeds
the upper
the thresholds. If yes,
threshold 278 V
contact the electric
power company.
or is less than
the lower
threshold 80 V.
PFC
Contact Huawei
soft-startup
technical support.
fails.
The power
module is
faulty.
Output
Reduce loads or
overload or
troubleshoot the
short-circuit
short-circuited load.
exists.
The
Install more air
UPS5000-E
conditioners or
inverter
ventilation devices to
temperature
ensure normal
exceeds the
temperatures inside the
upper
equipment room.
threshold.
The power
Contact Huawei
technical support.
module is
faulty.
The UPS is set
Set the UPS working
to ECO mode.
mode correctly.
The number of
Reset the bypass
bypass transfer
transfer times on the
times reaches
LCD.
the upper
threshold.