Huawei IDS1000-A Maintenance Manual page 75

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Fault
Category
Issue 01 (2016-01-10)
Alarm
Symptom
Severity
Major
The heating
function does not
work.
The electric heater
circuit breaker is
switched off.
The electric heater
burns out.
Major
Water overflows.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The electric
Check the temperature
heater
switch and replace it if
it is faulty.
temperature
switch is
protected.
The electric
Check the electric
heater circuit
heater circuit breaker.
breaker is
switched off.
The electric
Disconnect the power
heater burns
supply and check
out.
whether the heater is
damaged by measuring
its resistance with a
multimeter.
The drainpipe
Ensure that the
is not
drainpipe is correctly
connected to
connected to the pump,
the pump, or
and that the height of
the lift of the
the drainpipe is lower
condensate
than 3.5 meters.
pump does not
match the
height of the
pipes.
The water
Check the circuit
pump circuit
breaker status and cable
breaker or
connections.
cable
connection is
faulty.
1. Check the alarms
The water
displayed.
pump is faulty.
2. Verify pump cable
connections.
3. Rotate the pump
exhaust plug to
expel air, and close
the plug.
4. Check whether the
water pump is
working properly.
4 Alarms and Faults
67