Huawei IDS1000-A Maintenance Manual page 22

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Item
Issue 01 (2016-01-10)
Method
Expected
Result
Observe the liquid
The sight glass
loop sight glass.
is green.
Wear working
There is no oil
gloves and touch
stain.
the compressor
angle valve, needle
valve, and
soldering points in
the cooling circuit
to check whether
there are oil stains.
Check the pipes of
There is no
the humidifier
water stain
cylinder.
under pipes.
Check the thermal
The thermal
insulation foam.
insulation
foam is
properly
wrapped.
Check the indoor
The indoor fan
fans.
guards are not
misshapen, and
the fan blades
are intact.
Fans are
working
properly.
Screws
securing the
fan are not
loose or
misshapen.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
If the sight glass completely
turns yellow, there is too much
water in the pipe. To solve the
problem, discharge refrigerant
from the pipe, vacuumize the
system, drain out water, and then
charge new refrigerant.
If the sight glass does not
obviously turn green, use a blow
drier to blow wind to the filter
until the sight glass turns green.
Check whether the air suction and
exhaust pressure of the compressor
is within the normal ranges. If no,
contact Huawei technical support.
If drops of water are evenly
distributed, wipe off them with a
dry cloth.
If there are dense water stains,
identify the leakage point, close
the water inlet sluice, and repair
the leakage point.
Replace the thermal insulation foam
if it is damaged or missing. For
details, see
5.2.6 Replacing a
Thermal Insulation
Layer.
Replace the fans by following
instructions in the air conditioner
user manual.
Take out the foreign matter if the
fan is blocked.
Tighten the screws using a 10#
socket wrench.