Emergency Operations For Container Door Cannot Open - Huawei IDS1000-A Maintenance Manual

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Step 3 Open doors of the power supply or battery compartment to dissipate the hydrogen.
Do not use open flames or generate sparks in and around the IDS1000.
Step 4 Troubleshoot by referring to
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.8 Emergency Operations for Container Door Cannot
Open
Prerequisites
You cannot go into or out of the container.
Procedure
Step 1 Open the door using the emergency door release button.
The emergency door release button is a one-off component. You can remove the glass cover
of the emergency door release button and open the container door if you are not in an
emergent situation.
Step 2 Enter the container and check the devices.
Step 3 Locate the cause why the container door cannot be opened after verifying that the devices are
running properly.
Issue 01 (2016-01-10)
Possible causes why a container door cannot be opened are as follows:
The access card is faulty. Replace the access card and assign the access permission.
The card reader is faulty. Replace it by following instructions in
The exit button is faulty. Replace it by following instructions in
The magnetic lock is faulty. Replace it by following instructions in
Lock.
The fingerprint scanner is faulty. Replace it by following instructions in
Fingerprint
Scanner.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4.14 Hydrogen
Alarm.
6 Emergency Operations
5.3.13.1 Replacing a Card
Reader.
5.3.13.2 Replacing an Exit
Button.
5.3.13.3 Replacing a Magnetic
5.3.13.6 Replacing a
156