Huawei IDS1000-A Maintenance Manual page 59

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Alarm or
Fault
Battery
Electrolyte
Leakage
Overtemperatur
e
Management
System
Communication
Failure
High Hydrogen
Density
Container Door
Cannot Open
Container Door
Open Alarm
Early Fire
Alarm
Single Fire
Alarm
(Standard)
Issue 01 (2016-01-10)
Find Through
Possible Cause
Maintenance or
The battery is
equipment
damaged.
alarms
System and
equipment
alarms or
maintenance
System or
The circuit is
faulty.
equipment
alarms
System and
The hydrogen
equipment
exhaust fan is
faulty.
alarms or
maintenance
Maintenance
System and
The container
equipment
door is open.
alarms or
maintenance
System and
There is slight
equipment
smoldering in the
alarms or
data center.
maintenance
System and
A smoke alarm
equipment
or temperature
alarms or
alarm is
maintenance
generated.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Impact
The battery
cannot work
properly.
The cooling
Equipment
system is set
operation is
incorrectly.
adversely
affected.
A detector is
faulty.
Realtime
monitoring
cannot be
performed.
A fire or
explosion may
occur.
The controller
O&M
is faulty.
personnel
cannot go into
The circuit is
or out of the
faulty.
container.
Safety of the
equipment may
be affected.
A fire occurs.
A fire occurs.
4 Alarms and Faults
Emergency
Operation
6.4 Emergency
Operations for
Battery
Electrolyte
Leakage
6.5 Emergency
Operations for
Overtemperatu
re
6.6 Emergency
Operations for
the
Management
System
Communicatio
n Failure
6.7 Emergency
Operations for
High
Hydrogen
Density
6.8 Emergency
Operations for
Container
Door Cannot
Open
6.9 Emergency
Operations for
Container
Door Open
6.10
Emergency
Operations for
an Early Fire
Alarm
6.11
Emergency
Operations for
a Single Fire
Alarm
(Standard)
51