IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Item
UPS2000-G
UPS5000-E
batteries
Issue 01 (2016-01-10)
Method
Expected
Result
View the
The status
monitoring panel
icons on the
of the UPS5000-E.
LCD indicate
that all units
are operating
properly, all
operating
parameters are
within their
normal ranges,
and no fault or
alarm
information is
displayed.
UPS operating
status.
Check whether
the run
indicator on the
UPS is normal.
If the UPS is
faulty, the UPS
LCD displays
an alarm and
buzzes.
View records
about historical
alarms on the
Alarms menu
bar to check
whether an
alarm has been
generated.
View batteries.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
If an alarm is present, refer to the
UPS5000-E alarm reference to
check the device status and
parameters.
If the
Replace the UPS if it is faulty.
indicator is
steady
green, the
UPS is
working
properly.
If no alarm
is
generated,
the alarm
history
column
contains no
record.
1. Clean the batteries.
The battery
shell is
2. Take photos of the misshapen
intact,
parts and faulty parts of
without
batteries.
acid leaks,
3. Check and record the charge
deformatio
voltage and charge current of the
n, or
battery string, and the voltage of
bulges.
every single battery in this
battery string.
The battery
is free from
4. Check the battery surface
dust or dirt.
temperature.
5. Power off the battery string and
remove faulty batteries. After 30
minutes, check and record the
open-circuit voltages of the
faulty batteries.
3 Maintenance
11