6.3 Overload Emergency Operations

Prerequisites
An overload alarm is generated.
Procedure
Step 1 Locate the cable or device based on the alarm information.
Step 2 Check the overloaded cable or device and locate the fault.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.

6.4 Emergency Operations for Battery Electrolyte Leakage

Prerequisites
The battery electrolyte leaks.
Procedure
Step 1 Switch off the circuit breaker corresponding to the battery string where the electrolyte leakage
occurs.
Step 2 Replace the battery that has electrolyte leakage. For details, see
Battery.
Before the replacement, get ready protective gloves and the tool used to clean the electrolyte.
Step 3 After replacing the battery and cleaning the leaked electrolyte, verify that the battery is
properly connected in the UPS5000-E system.
Step 4 Check that the battery is ready for power-on, and switch on the circuit breaker in the battery
cabinet.
----End
Issue 01 (2016-01-10)
If the cable or device is seriously overloaded, immediately power off the device and its lower-level
devices.
Ignore the alarm generated after the circuit breaker in the cabinet is switched off.