All-in-One Maintenance Guide
Item
Hand-held
fire
extinguisher

3.2.5 Fire Extinguishing System (CE)

Table 3-6 Monthly maintenance checklist for the fire extinguishing system
Item
Fire control
panel
Fire
extinguisher
Issue 01 (2016-01-10)
Method
Expected
Result
Check the fire
The fire
extinguisher.
extinguisher is
intact.
The fire
extinguisher is
within the
validity
period.
Method
Expected Result
Check indicators
The power indicator
on the fire control
is on, and the alarm
panel.
indicator is off.
Check the fire
The components are
cylinder, solenoid
not misshapen due to
driver, pipes, and
collision and have no
nozzles.
mechanical damage.
The components do
not rust on the
exterior, the coating
is intact, and the
nameplates are
clearly legible.
The protective cover,
lead seal, and safety
signs on
hand-operated
devices are intact.
Read the pressure
The pressure pointer
shown on the
is in the green zone.
pressure gauge.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
If the fire extinguisher is damaged,
replace it.
If the fire extinguisher has expired,
replace it.
Troubleshooting
Replace a faulty component
by following instructions in
Fire Alarm Controller/Fire
Control Panel User Manual
or
5.5.9 Replacing a Fire
Control
Panel.
Replace by following
instructions in
5.5.8
Replacing a Fire
Cylinder.
For details about how to
replace other components,
contact Huawei technical
support.
Repair the paint.
Replace a faulty component.
Contact the local
maintenance engineers for
prompt pressure increase.