IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Preparations
Tool: flat-head screwdriver, step ladder (2 m)
Material: spare remote T/H sensor
Documents required: initial configuration parameters for cooling devices
Skill requirement: cooling engineer
Procedure
Step 1 Remove the network cable from the remote T/H sensor, as shown in
Figure 5-7 Removing the network cable from the remote T/H sensor
Step 2 Remove the faulty remote T/H sensor, install a new remote T/H sensor, and reconnect the
network cable to the sensor.
Step 3 Set the DIP switch for the remote T/H sensor by referring to the remote T/H sensor DIP
switch initial configuration table.
Step 4 Check that the new remote T/H sensor is working properly.
----End
Follow-up Procedure
Dispose of the removed remote T/H sensor that is confirmed faulty.
Issue 01 (2016-01-10)
For the table, see the initial configuration guide.
Verify that the indicator on the remote T/H sensor is on.
Verify that there is no remote T/H sensor communication failure on the air conditioner panel.