YASKAWA E1000 Technical Manual page 177

For fan and pump
Table of Contents

Advertisement

E5-01: Motor Code Selection
When Yaskawa motors are used, set the motor code for the PM motor being used. Depending on the motor code entered,
the drive automatically sets several parameters to appropriate values.
Code Selection on page 404
Setting parameter E5-01 to FFFF will allow to set the motor data manually using the E5- parameters.
No.
E5-01
Note: 1. E5- parameters are not reset when the drive is initialized using parameter A1-03.
2. When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-03.
3. Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.
4. Set E5-01 to FFFF when using a motor other than a Yaskawa SMRA, SSR1, or SST4 series.
Figure 5.30
explains the motor code setting.
Figure 5.30
E5-02: Motor Rated Power
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors or
by entering the motor code to E5-01.
No.
E5-02
<1> The display resolution depends on the motor rated power. Drive models 2A0004 to 2A0415 and 4A0002 to 4A0515 will display this value in
units of 0.01 kW (two decimal places). Models 4A0675 to 4A1200 will display this value in units of 0.1 kW (one decimal place).
Model Number and Nameplate Check on page 29
E5-03: Motor Rated Current
Sets the motor rated current in amps. This parameter is automatically set when the value is entered to T2-06 during the
Auto-Tuning process.
No.
E5-03
Note: This value's number of decimal places depends on the drive model. The value will have two decimal places (0.01 A) if the drive
is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to
if the set Maximum Applicable Motor Capacity is higher than 11 kW.
E5-04: Number of Motor Poles
Sets the number of motor poles. This parameter is automatically set when the value is entered to T2-08 during the Auto-
Tuning process.
No.
E5-04
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
for details on the supported motor codes and their parameter settings.
Parameter Name
Motor Code Selection
0 0 0 0
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
2: Rated Torque for IPM
Motors
Figure 5.30 PM Motor Code
Parameter Name
Motor Rated Power
for details.
Parameter Name
Motor Rated Current
Parameter Name
Number of Motor Poles
Refer to Parameters that Change with the Motor
Setting Range
0000 to FFFF
Motor Voltage Class
and Capacity
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
YEC_TMonly
Setting Range
0.10 to 650.00 kW
Setting Range
10 to 200% of drive rated current
Table A.1
and
Table
A.2) and one decimal place (0.1 A)
Setting Range
2 to 48
5.5 E: Motor Parameters
Default
Determined by o2-04
Default
Determined by E5-01
<1>
Refer to
Default
Determined by E5-01
Default
Determined by E5-01
5
177