Switching Between Local And Remote - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

4.3 The Drive and Programming Modes
Parameter
A1-02
Control Method Selection
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-03
Stopping Method Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-02
Carrier Frequency Selection
d2-01
Frequency Reference Upper Limit
d2-02
Frequency Reference Lower Limit
E1-01
Input Voltage Setting
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E2-01
Motor Rated Current
E2-11
Motor Rate Power
F6-01
Communications Error Operation Selection
Note: Parameter availability depends on the control mode set in A1-02 that is used to run the drive and motor. Consequently, some of
the parameters listed above may not be accessible in certain control modes.

◆ Switching Between LOCAL and REMOTE

When the drive is set to accept the Run command from the digital operator RUN key, this is referred to as LOCAL mode.
When the drive is set to accept the Run command from an external device (via the input terminals, serial
communications, etc.) this is referred to as REMOTE mode.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating
machinery.
The operation can be switched between LOCAL and REMOTE either by using the LO/RE key on the digital operator or
a digital input.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
Using the LO/RE Key on the Digital Operator
1.
Turn on the power to the drive. The initial display appears.
Press
. The LO/RE light will light up. The drive is now in LOCAL.
2.
To set the drive for REMOTE operation, press the
Using Input Terminals S1 through S8 to Switch between LO/RE
The user can also switch between LOCAL and REMOTE modes using one of the digital input terminals S1 through S8
(set the corresponding parameter H1- to "1").
When setting the multi-function input terminals,
Note: 1.
Refer to Parameter Table on page 360
2. Setting H1- to 1 disables the LO/RE key on the digital operator.
106
Table 4.4 Setup Group Parameters
Name
Step
key again.
for a list of digital input selections.
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Parameter
H3-03
Terminal A1 Gain Setting
H3-04
Terminal A1 Bias Setting
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Bias Setting
L2-01
Momentary Power Loss Operation Selection
L2-02
Momentary Power Loss Ride Thru Time
L4-05
Frequency Reference Loss Detection Selection
L4-06
Frequency Reference at Reference Loss
L5-01
Number of Auto Restart Attempts
L5-03
Time to Continue Making Fault Restarts
L6-01
Torque Detection Selection 1
L6-02
Torque Detection level 1
L6-03
Torque Detection Time 1
o2-03
User Parameter Default Value
o2-05
Frequency Reference Setting Method Selection
Name
Display/Result
YEC_c
DIGITAL OPERATOR JVOP-182
ALM
DRV
ommon
REV
DRV
FOUT
DIGITAL OPERATOR JVOP-182
ALM
DRV
REV
DRV
FOUT
YEC_
com -
LO
ESC
RE
mon
RESET
ENTER
RUN
STOP