H6-01: Pulse Train Input Terminal RP Function Selection
Selects the function of pulse train input terminal RP.
No.
H6-01
Setting 0: Frequency reference
If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01, b1-15 = 4), the
drive reads the frequency value from terminal RP.
Setting 1: PI feedback value
Using this setting, the feedback value for PI control can be supplied as a pulse signal at terminal RP.
Control on page 145
for details on PI control.
Setting 2: PI setpoint value
Using this setting, the setpoint value for PI control can be supplied as a pulse signal at terminal RP.
Control on page 145
for details on PI control.
H6-02: Pulse Train Input Scaling
This parameter sets the pulse signal frequency that is equal to 100% of the input value selected in parameter H6-01.
No.
H6-02
H6-03: Pulse Train Input Gain
Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to
terminal RP.
No.
H6-03
H6-04: Pulse Train Input Bias
Sets the level of the input value selected in H6-01 when no signal (0 Hz) is input to terminal RP.
No.
H6-04
H6-05: Pulse Train Input Filter Time
Sets the pulse train input filter time constant in seconds.
No.
H6-05
H6-06: Pulse Train Monitor Selection
Selects the monitor to output as a pulse train signal via terminal MP. Indicate which monitor to output entering the three
digits in U-.
Refer to U: Monitor Parameters on page 253
selected by H6-06 appear in the table below.
No.
H6-06
<1> Set "000" when the terminal is not used, or when using the terminal in the through mode.
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Name
Pulse Train Input Terminal RP Function Selection
Name
Pulse Train Input Scaling
Name
Pulse Train Input Gain
Name
Pulse Train Input Bias
Name
Pulse Train Input Filter Time
Name
Pulse Train Monitor Selection
5.7 H: Terminal Functions
Setting Range
0 to 2
Setting Range
100 to 32000 Hz
Setting Range
0.0 to 1000.0%
Setting Range
-100.0 to 100.0%
Setting Range
0.00 to 2.00 s
for a complete list of monitors. Monitors that can be
Setting Range
000
, 031, 101, 102, 116, 501, 502,
<1>
801 to 809
Default
0
Refer to b5: PI
Refer to b5: PI
Default
1440 Hz
Default
100.0%
Default
0.0%
Default
0.10 s
5
Default
102
207