B.3 Parameter Table
H1-
Function
Setting
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer Function Input
19
PI Disable
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PI Integral Reset
31
PI Integral Hold
34
PI Soft Starter Cancel
35
PI Input Level Selection
36
External Reference 1/2 Selection 2
374
H1 Multi-Function Digital Input Selections
All Modes
Select this setting when using the terminal in a pass-through mode. The terminal does not trigger a drive function
but can be used as digital input for the controller the drive is connected to.
All Modes
The drive accelerates when the Up command terminal closes, and decelerates when the Down command closes.
When both terminals are closed or both are open, the drive holds the frequency reference. The Up and Down
commands must always be used in conjunction with one another.
All Modes
Closed: Runs forward at the Jog frequency d1-17.
All Modes
Closed: Runs reverse at the Jog frequency d1-17.
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
All Modes
Closed: Decelerates at the Fast Stop time set to C1-09.
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2- = 12).
All Modes
Open: PI control enabled
Closed: PI control disabled
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
All Modes
Closed: Samples the analog frequency reference and operates the drive at that speed.
All Modes
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
All Modes
Closed: Resets the PI control integral value.
All Modes
Open: Performs integral operation.
Closed: Maintains the current PI control integral value.
All Modes
Open: PI soft starter is enabled.
Closed: Disables the PI soft starter b5-17.
All Modes
Closed: Inverts the PI input signal
All Modes
Open: Run command and frequency reference source 2 (determined by b1-15 and b1-16)
Closed: Run command and frequency reference source 1 (determined by b1-01 and b1-02)
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Description
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
Page
184
184
184
185
185
185
185
185
186
186
186
186
186
187
187
187
187
187

Advertisement

Table of Contents
loading

Table of Contents