C: Tuning - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

B.3 Parameter Table
No.(Addr.)
Name
b8-06
Search Operation Voltage Limit
(1D1H)
<8> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<9> Default setting value is dependent on the drive model (o2-04).
<10> Default setting is determined by the control mode (A1-02).

◆ C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier
frequency selections.
C1: Acceleration and Deceleration Times
No.(Addr.)
Name
C1-01
(200H)
Acceleration Time 1
C1-02
(201H)
Deceleration Time 1
C1-03
(202H)
Acceleration Time 2
C1-04
(203H)
Deceleration Time 2
C1-09
Fast Stop Time
(208H)
C1-11
Accel/Decel Time Switching
(20AH)
Frequency
C2: S-Curve Characteristics
No.(Addr.)
Name
C2-01
S-Curve Characteristic at Accel
(20BH)
Start
C2-02
S-Curve Characteristic at Accel
(20CH)
End
<10> Default setting is determined by the control mode (A1-02).
C4: Torque Compensation
No.(Addr.)
Name
C4-01
(215H)
Torque Compensation Gain
C4-02
(216H)
Torque Compensation Primary
Delay Time
<10> Default setting is determined by the control mode (A1-02).
<16> Default setting is determined by the control mode (A1-02) and the drive model (o2-04).
366
V/f
OLV/PM
Sets the limit for the voltage search operation as a percentage of the motor rated voltage.
All Modes
Sets the time to accelerate from 0 to maximum frequency.
All Modes
Sets the time to decelerate from maximum frequency to 0.
All Modes
Sets the time to accelerate from 0 to maximum frequency.
All Modes
Sets the time to decelerate from maximum frequency to 0.
All Modes
Sets the time for the Fast Stop function.
All Modes
Sets the frequency for automatic switching of Accel/ Decel times.
All Modes
The S-curve can be controlled at the four points shown below.
Run Command
Output Frequency
<1> S-Curve Charactaristic at Decel Start/End are fixed to 0.20 s.
V/f
OLV/PM
Sets the gain for the automatic torque (voltage) boost function and helps to produce better
starting torque.
V/f
OLV/PM
Sets the torque compensation filter time.
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Description
Description
Description
ON
OFF
C2-02
0.20 s <1>
C2-01
0.20 s <1>
Time
Description
Setting
Default: 0%
common_
TMonly
Min: 0%
Max: 100%
Setting
common_
TMonly
common_
TMonly
Default: 30.0 s
Min: 0.0 s
Max: 6000.0 s
common_
TMonly
common_
TMonly
common_
Default: 10.0 s
TMonly
Min: 0.0 s
Max: 6000.0 s
common_
Default: 0.0 Hz
TMonly
Min: 0.0 Hz
Max: 200.0 Hz
Setting
common_
TMonly
Default:
<10>
Min: 0.00 s
Max: 10.00 s
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
Setting
common_
Default:
<10>
TMonly
Min: 0.00
Max: 2.50
Default:
common_
<16>
TMonly
Min: 0 ms
Max: 60000 ms
Page
159
Page
160
160
160
160
161
161
Page
162
162
Page
162
163