5.7 H: Terminal Functions
Figure 5.49
Frequency
Detection 4
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 227
Setting 1A: During Reverse
A digital output set for "During reverse" will close whenever the drive is running the motor in the reverse direction.
Status
Open
Motor is being driven in the forward direction or stopped.
Closed
Motor is being driven in reverse.
Figure 5.50
Setting 1B: During Baseblock (N.C.)
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Status
Open
Baseblock is being executed.
Closed
Drive is not in a baseblock state.
Setting 1E: Restart Enabled
An output set for "Restart enabled" closes once the drive begins attempting to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has begun attempting to restart. If the drive cannot successfully restart within the number of
attempts permitted by L5-01, then a fault will be triggered and the terminal set to 1E will open.
Restart on page 228
for details on automatic restart.
Setting 1F: Motor Overload Alarm (oL1)
An output programmed for this function will close when the motor overload level estimated by the oL1 fault detection
exceeds 90% of the oL1 detection level.
Setting 20: Drive Overheat Pre-alarm (oH)
Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02.
Overheat Alarm Level on page 233
196
Output Frequency
or Motor Speed
OFF
ON
Figure 5.49 Frequency Detection 4 Example with Positive L3-04 Value
Output frequency
FWD Run command
REV Run command
During Reverse
Figure 5.50 Reverse Direction Output Example Time Chart
Refer to L1-01: Motor Overload Protection Selection on page
for details on drive overheat detection.
L4-04
L4-03
Description
ON
OFF
Description
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
common_
TMonly
for more details.
common_
TMonly
time
Refer to L5: Fault
209.
Refer to L8-02: