YASKAWA E1000 Technical Manual page 152

For fan and pump
Table of Contents

Advertisement

5.2 b: Application
The parameters necessary that control the PI Sleep/Snooze function are explained below.
PI Setpoint
PI Feedback
b5-15: PI Sleep Function Start Level
Sets the level that triggers PI Sleep.
The drive goes into Sleep mode if the PI output or frequency reference is smaller than b5-15 for longer than the time set
in b5-16. It resumes the operation when the PI output or frequency reference is above b5-15 for longer than the time set
in b5-16.
No.
b5-15
b5-16: PI Sleep Delay Time
Sets the delay time to activate or deactivate the PI Sleep function.
No.
b5-16
152
b5-25 PI Setpoint
Boost Setting
b5-27 Snooze
Feedback Level
SFS Output frequency
t<b5-23
b5-22
PI Snooze Level
PI operation
Snooze function activated
Name
PI Sleep Function Start Level
Name
PI Sleep Delay Time
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
common_TMonly
b5-26 PI Boost
PI Setpoint+ b5-25
Maximum Time
b5-23
PI Snooze
Delay Time
Boost
Time
b5-24
PI Snooze
Deactivation
Level
Time
Deceleration
Time
Snooze mode
PI operation
Setting Range
0.0 to 200.0 Hz
Setting Range
0.0 to 25.5 s
Default
0.0 Hz
Default
0.0 s