YASKAWA E1000 Technical Manual page 386

For fan and pump
Table of Contents

Advertisement

B.3 Parameter Table
No. (Addr.)
Name
L8-07
Output Phase Loss Protection
(4B3H)
Selection
L8-09
Output Ground Fault Detection
(4B5H)
Selection
L8-10
Heatsink Cooling Fan Operation
(4B6H)
Selection
L8-11
Heatsink Cooling Fan Off-Delay
(4B7H)
Time
L8-12
Ambient Temperature Setting
(4B8H)
L8-15
oL2 Characteristics Selection at
(4BBH)
Low Speeds
L8-18
Software Current Limit Selection
(4BEH)
L8-19
Frequency Reduction Rate during
(4BFH)
Overheat Pre-Alarm
L8-27
Overcurrent Detection Gain
(4DDH)
L8-29
Current Unbalance Detection
(4DFH)
(LF2)
L8-32
Main Contactor and Cooling Fan
(4E1H)
Power Supply Failure Selection
L8-35
Installation Method Selection
(4ECH)
L8-38
Carrier Frequency Reduction
(4EFH)
Selection
L8-40
Carrier Frequency Reduction Off-
(4F1H)
Delay Time at Start
L8-41
High Current Alarm Selection
(4F2H)
L8-78
Power Unit Output Phase Loss
(2CCH)
Protection
<3> Parameter setting value is not reset to the default value when the drive is initialized.
<9> Default setting is determined by the drive model (o2-04).
<10> Default setting is determined by the control mode (A1-02).
<16> Default setting is determined by the control mode (A1-02) and the drive model (o2-04).
386
All Modes
0: Disabled
1: Enable (triggered when single phase is lost)
2: Enabled (triggered when two phases are lost)
All Modes
0: Disabled
1: Enabled
All Modes
0: Run with timer. Fan operates only during run and for L8-11 seconds after stop.
1: Run always. Cooling fan operates whenever the drive is powered up.
All Modes
Sets a delay time to shut off the cooling fan after the Run command is removed when L8-10 = 0.
All Modes
Enter the ambient temperature. This value adjusts the oL2 detection level.
All Modes
0: Protection disabled at low speed.
1: Protection enabled at low speed.
V/f
OLV/PM
0: Software CLA disabled (gain=0)
1: Software CLA enabled
All Modes
Specifies the frequency reference reduction gain at overheat pre-alarm when L8-03 = 4.
V/f
OLV/PM
Sets the gain for overcurrent detection as a percentage of the motor rated current. Overcurrent is
detected using the drive's overcurrent level or the value set to L8-27, whichever is lower.
V/f
OLV/PM
0: Disabled
1: Enabled
All Modes
Determines the action the drive should take when a fault occurs with the internal cooling fan.
0: Ramp to stop with C1-02
1: Coast to stop
2: Ramp to stop with fast stop C1-09
3: Alarm only
All Modes
0: IP00 enclosure
1: Side-by-Side mounting
2: IP20/NEMA 1, UL Type 1 enclosure
3: Finless drive or external heatsink installation
All Modes
0: Disabled
1: Enabled for output frequencies below 6 Hz
2: Enabled for the entire frequency range
All Modes
Sets the time that the drive continues running with reduced carrier frequency after the carrier
reduction condition is gone. Setting 0.00 s disables the carrier frequency reduction time.
All Modes
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150% of the drives rated current.
All Modes
Enables motor protection if output phase loss occurs.
0: Disabled
1: Enabled
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Description
Setting
common_
TMonly
Default: 0
Min: 0
Max: 2
common_
Default:
<9>
TMonly
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
Default: 60 s
common_
TMonly
Min: 0 s
Max: 300 s
Default: 40°C
common_
TMonly
Min: -10°C
Max: 50°C
common_
Default: 1
TMonly
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
Default: 0.8
common_
TMonly
Min: 0.1
Max: 0.9
common_
Default: 300.0%
TMonly
Min: 0.0%
Max: 300.0%
common_
Default: 1
TMonly
Min: 0
Max: 1
common_
TMonly
Default: 1
Min: 0
Max: 4
common_
TMonly
Default:
<3> <9>
Min: 0
Max: 3
common_
TMonly
Default:
<16>
Min: 0
Max: 2
common_
Default:
<10>
TMonly
Min: 0.00 s
Max: 2.00 s
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
TMonly
Default: 1
Min: 0
Max: 1
Page
235
235
236
236
236
236
236
234
237
237
237
237
238
238
238
239

Advertisement