B.5 V/f Pattern Default Values
The tables below show the V/f pattern settings default values depending on the control mode (A1-02) and the V/f pattern
selection (E1-03 in V/f Control).
No.
Units
E1-03
-
0
1
E1-04
Hz
50.0
60.0
E1-05
V
200.0
200.0
<18>
E1-06
Hz
50.0
60.0
E1-07
Hz
2.5
3.0
E1-08
V
15.0
15.0
<18>
E1-09
Hz
1.3
1.5
E1-10
V
9.0
9.0
<18>
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10.
No.
Units
E1-03
-
0
1
E1-04
Hz
50.0
60.0
E1-05
V
200.0
200.0
<18>
E1-06
Hz
50.0
60.0
E1-07
Hz
2.5
3.0
E1-08
V
14.0
14.0
<18>
E1-09
Hz
1.3
1.5
E1-10
V
7.0
7.0
<18>
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10.
No.
Units
E1-03
-
0
1
E1-04
Hz
50.0
60.0
E1-05
V
200.0
200.0
<18>
E1-06
Hz
50.0
60.0
E1-07
Hz
2.5
3.0
E1-08
V
12.0
12.0
<18>
E1-09
Hz
1.3
1.5
E1-10
V
6.0
6.0
<18>
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10.
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Table B.3 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-E2A0004 to 2A0021, CIMR-E4A0002 to 4A0011
2
3
4
5
6
60.0
72.0
50.0
50.0
60.0
200.0
200.0
200.0
200.0
200.0
50.0
60.0
50.0
50.0
60.0
3.0
3.0
25.0
25.0
30.0
15.0
15.0
35.0
50.0
35.0
1.5
1.5
1.3
1.3
1.5
9.0
9.0
8.0
9.0
8.0
Table B.4 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-E2A0030 to 2A0211, CIMR-E4A0018 to 4A0103
2
3
4
5
6
60.0
72.0
50.0
50.0
60.0
200.0
200.0
200.0
200.0
200.0
50.0
60.0
50.0
50.0
60.0
3.0
3.0
25.0
25.0
30.0
14.0
14.0
35.0
50.0
35.0
1.5
1.5
1.3
1.3
1.5
7.0
7.0
6.0
7.0
6.0
Table B.5 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-E2A0250 to 2A0415, CIMR-E4A0139 to 4A1200
2
3
4
5
6
60.0
72.0
50.0
50.0
60.0
200.0
200.0
200.0
200.0
200.0
50.0
60.0
50.0
50.0
60.0
3.0
3.0
25.0
25.0
30.0
12.0
12.0
35.0
50.0
35.0
1.5
1.5
1.3
1.3
1.5
6.0
6.0
5.0
6.0
5.0
V/f
7
8
9
A
B
60.0
50.0
50.0
60.0
60.0
200.0
200.0
200.0
200.0
200.0
60.0
50.0
50.0
60.0
60.0
30.0
2.5
2.5
3.0
3.0
50.0
19.0
24.0
19.0
24.0
1.5
1.3
1.3
1.5
1.5
9.0
11.0
13.0
11.0
15.0
V/f
7
8
9
A
B
60.0
50.0
50.0
60.0
60.0
200.0
200.0
200.0
200.0
200.0
60.0
50.0
50.0
60.0
60.0
30.0
2.5
2.5
3.0
3.0
50.0
18.0
23.0
18.0
23.0
1.5
1.3
1.3
1.5
1.5
7.0
9.0
11.0
9.0
13.0
V/f
7
8
9
A
B
60.0
50.0
50.0
60.0
60.0
200.0
200.0
200.0
200.0
200.0
60.0
50.0
50.0
60.0
60.0
30.0
2.5
2.5
3.0
3.0
50.0
15.0
20.0
15.0
20.0
1.5
1.3
1.3
1.5
1.5
6.0
7.0
9.0
7.0
11.0
B.5 V/f Pattern Default Values
F
C
D
E
<42>
90.0
120.0
180.0
50.0
200.0
200.0
200.0
200.0
60.0
60.0
60.0
50.0
3.0
3.0
3.0
2.5
15.0
15.0
15.0
15.0
1.5
1.5
1.5
1.3
9.0
9.0
9.0
9.0
F
C
D
E
<42>
90.0
120.0
180.0
50.0
200.0
200.0
200.0
200.0
60.0
60.0
60.0
50.0
3.0
3.0
3.0
2.5
14.0
14.0
14.0
14.0
1.5
1.5
1.5
1.3
7.0
7.0
7.0
7.0
F
C
D
E
<42>
90.0
120.0
180.0
50.0
200.0
200.0
200.0
200.0
60.0
60.0
60.0
50.0
3.0
3.0
3.0
2.5
12.0
12.0
12.0
12.0
1.5
1.5
1.5
13
6.0
6.0
6.0
6.0
OLV/PM
<14>
<14>
<14>
<14>
OLV/PM
<14>
<14>
<14>
<14>
OLV/PM
<14>
<14>
<14>
<14>
B