YASKAWA E1000 Technical Manual page 428

For fan and pump
Table of Contents

Advertisement

C.9 MEMOBUS/Modbus Data Table
Register No.
003EH
Output Frequency
003FH
0040H to 004AH
Used for various monitors U1-.
Drive status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
004BH
bit 6
bit 7
bit 8
bit 9
bit A to bit B
bit E
bit F
004CH to 007EH
Used for various monitors U1-, U4-, U5- and U6-.
007FH
Alarm Code,
Used for monitors U2-, U3-.
0080H to 0097H
value descriptions.
0098H
High Word of Accumulated Operation Time Monitor, 10H units (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor, 1H units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
00AEH, 00AFH
Reserved
00B0H
Option Code Connected to CN5-A
00B1H–00B4H
Reserved
00B5H
Frequency Reference After Soft-
starter (U1-16)
00B6H
00B7H
Frequency Reference
00B8H
00B9H to 00BEH
Reserved
00BFH
Lists the last to digits of operation error code oPE.
Fault contents 3
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
00C0H
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D to F
Fault contents 4
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
00C1H
bit 6
bit 7 to bit 9
bit A
bit B
bit C
bit D
bit E
bit F
428
r/min
<4>
0.01% units
Refer to U: Monitors on page 391
During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault
During Operation Error (oPE)
During Momentary Power Loss
Reserved
ComRef status, NetRef status
ComCtrl status, NetCtrl status
Refer to Alarm Register Contents on page 433
Refer to U: Monitors on page 391
<2>
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type number.
Example: Register value is 5343H for "SC" if a SI-C3 option card is installed.
r/min units
<4>
0.01% units
r/min
<4>
0.01% units
Undervoltage (Uv1)
Control Power Supply Undervoltage (Uv2)
Soft Charge Circuit Fault (Uv3)
IGBT Short Circuit (SC)
Ground Fault (GF)
Overcurrent (oC)
Overvoltage (ov)
Heatsink Overheat (oH)
Heatsink Overheat (oH1)
Motor Overload (oL1)
Drive Overload (oL2)
Overtorque Detection 1 (oL3)
Reserved
External Fault at input terminal S3 (EF3)
External Fault at input terminal S4 (EF4)
External Fault at input terminal S5 (EF5)
External Fault at input terminal S6 (EF6)
External Fault at input terminal S7 (EF7)
External Fault at input terminal S8 (EF8)
Cooling Fan Error (FAn)
Reserved
Input Phase Loss (PF)
Output Phase Loss (LF)
Motor Overheat (PTC input) (oH3)
Digital Operator Connection Fault (oPr)
EEPROM Write Error (Err)
Motor Overheat Fault (PTC input) (oH4)
Contents
for parameter details.
Refer to U: Monitors on page 391
for alarm codes.
for parameter details and
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
for parameter details.
Refer to Fault Trace Contents on page 432
for register