o1-05: LCD Contrast Control
Sets the brightness of the LCD operator (option). The lower the setting, the brighter the LCD. The higher the setting, the
darker the LCD.
No.
o1-05
o1-06: User Monitor Selection Mode
Normally the monitors shown directly below the active monitor are the next two sequential monitors. If o1-06 (User
Monitor Selection Mode) is set to "1: 3 Mon Selectable", those two monitors are locked as specified by parameters o1-07
and o1-08 and will not change as the top parameter is scrolled with the Up/Down Arrow keys.
No.
o1-06
0: 3 Monitor Sequential (Displays the next 2 sequential monitor)
1: 3 Monitor Selectable: o1-07, and o1-08 selected monitor is shown
o1-07: Second Line Monitor Selection
Selects which monitor will be displayed in the second line. The monitor parameter number is entered into the spaces
provided: U-.
For example, set "403" to display monitor parameter U4-03.
No.
o1-07
o1-08: Third Line Monitor Selection
Selects which monitor will be displayed in the third line. The monitor parameter number is entered into the spaces
provided: U-.
For example, set "403" to display monitor parameter U4-03.
No.
o1-08
o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency.
No.
o1-10
o1-11: User-Set Display Units Decimal Display
Determines how many decimal points should be used to set and display the frequency reference.
No.
o1-11
Setting 0: No decimal point
Setting 1: One decimal point
Setting 2: Two decimal points
Setting 3: Three decimal points
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Name
LCD Contrast Control
Name
User Monitor Selection Mode
Name
Second Line Monitor Selection
Name
Third Line Monitor Selection
Name
User-Set Display Units Maximum Value
Name
User-Set Display Units Decimal Display
5.10 o: Operator Related Settings
Setting Range
0 to 5
Setting Range
0, 1
Setting Range
101 to 825
Setting Range
101 to 825
Setting Range
1 to 60000
Determined by o1-03
Setting Range
0 to 3
Determined by o1-03
Default
3
Default
0
Default
102
Default
103
Default
5
Default
247