NOTE!
The operation of parameters P022 as well as of the frequency input, depends on the configuration of
the parameter P246.
P246 - FI1 Input Function
Range:
0 = Inactive
1 = Active in DI1
2 = Active in DI2
3 = Active in DI3
4 = Active in DI4
Properties:
cfg
Description:
When set to "0" the frequency input is inactive, keeping parameter P022 at zero. In the other cases, this parameter
activates the frequency input on the DIx, making any other function in this digital input DIx (P263-P266) be ignored,
and the value of its respective bit in parameter P012 is kept at "0". In order to do so, it is also necessary to configure
parameters P221 and/or P222, selecting the use of the frequency input.
P247 - FI1 Input Gain
Range:
0.000 to 9.999
Description:
It sets the gain of the frequency input.
P248 - FI1 Minimum Input
Range:
1 to 3000 Hz
Description:
It sets the minimum value of the frequency input.
P249 - FI1 Input Offset
Range:
-100.0 to 100.0 %
Description:
It sets the offset of the frequency input.
P250 - FI1 Maximum Input
Range:
1 to 3000 Hz
Description:
It sets the maximum value of the frequency input.

9.6 DIGITAL INPUTS

Below is a detailed description of the parameters for the digital inputs.
I/O
Micro Mini Drives | 9-11
9