External Frame Ground Point Rear View - Nokia 7360 Intelligent Services Access Manager FX Series Hardware Installation Manual

Ansi
Hide thumbs Also See for 7360 Intelligent Services Access Manager FX Series:
Table of Contents

Advertisement

ANSI Hardware Installation Manual
3
Figure 235
4
5
Issue: 09
Connect the grounding cable to one of the two frame grounding points on the top of the rack,
as shown in Figure 235, using the screws provided with the rack.

External frame ground point rear view

No. 6 AWG lug and 2 12-24 screws
(provided with the rack)
Frame ground point
Rack frame ground locations rear view
Perform power and ground tests as per local practices.
STOP. This procedure is complete.
3HH-12893-AAAA-TCZZA
Frame ground point