Nokia 7360 Intelligent Services Access Manager FX Series Hardware Installation Manual page 334

Ansi
Hide thumbs Also See for 7360 Intelligent Services Access Manager FX Series:
Table of Contents

Advertisement

Installing a 7360 ISAM FX-4 shelf
Procedure 72
Use this procedure to mount the 7360 ISAM FX-4 shelf vertically in a 23 in. rack; see Figure 191.
1
2
3
4
334
To mount the 7360 ISAM FX-4 shelf vertically in a 23 in. rack
Caution — The vertical shelf mount kit must be used for the
7360 ISAM FX-4 in a vertical mount installation as the air intake baffle/
drip tray and top baffle are required to meet NEBS preferred airflow
specifications (air flows in the front, and out the rear of the shelf).
Unpack and inspect the shelf vertical shelf mount kit visually for physical damage.
If anything is missing or damaged, notify the transportation carrier and Nokia immediately.
Photograph all the damaged equipment. Keep all the inspection and packing documents as
a reference.
Warning — Possibility of equipment damage.
Do not install damaged equipment, as it can adversely affect other
equipment.
Put on the antistatic wrist strap and connect it to a grounding point.
Verify the 7360 ISAM FX-4 shelf mounting locations on the rack; see Figure 187.
3HH-12893-AAAA-TCZZA
ANSI Hardware Installation Manual
DRAFT
Issue: 09