Installing A 7360 Isam Fx-8 Shelf; Overview - Nokia 7360 Intelligent Services Access Manager FX Series Hardware Installation Manual

Ansi
Hide thumbs Also See for 7360 Intelligent Services Access Manager FX Series:
Table of Contents

Advertisement

ANSI Hardware Installation Manual

13 Installing a 7360 ISAM FX-8 shelf

13.1 Overview

This chapter provides the steps to install a 7360 ISAM FX-8 shelf in a standard CO
equipment rack, including procedures for:
The 7360 ISAM FX-8 is suitable for the following:
Issue: 09
13.1 Overview
13.2 Mounting the 7360 ISAM FX-8 shelf in a 19 in. rack
13.3 Mounting the 7360 ISAM FX-8 shelf in a 23 in. rack
13.4 Installing or replacing a fan unit in a 7360 ISAM FX-8 shelf
Mounting the 7360 ISAM FX-8 shelf in a 19 in. rack
Mounting the 7360 ISAM FX-8 shelf in a 23 in. rack
Installing or replacing a fan unit in a 7360 ISAM FX-8 shelf
The 7360 ISAM FX-8 is intended to be installed in
Warning —
a restricted access location (RAL) in accordance with the
applicable requirements of NEC or CEC. The local authorities
have jurisdiction. This unit is intended to be installed by
qualified service personnel only. Observe the following for the
7360 ISAM FX-8.
Connect to a reliably grounded −48 V dc SELV source that
is grounded in the same building.
Provide branch circuit overcurrent protection that is rated as
50 A with 8 AWG copper conductors.
Incorporate a readily accessible disconnect device that is
suitably approved and rated in the field wiring.
rack mounting on concrete floors or other non-combustible surfaces with the use
of a drip tray
use in an installation using an IBN or a CBN
use in:
network telecommunication facilities
locations where the NEC applies
OSP
3HH-12893-AAAA-TCZZA
DRAFT

Installing a 7360 ISAM FX-8 shelf

223