7360 ISAM FX-4 shelf cabling
Figure 193
Procedure 75
Use the following procedures to connect the grounding cable.
1
2
3
346
Grounding cable connection on 7360 ISAM FX-4
To connect the grounding cable
Route the grounding cable to the right side of the shelf and up to the middle of the shelf.
Connect the dual-lug to the grounding cable connection point as shown in Figure 193.
Danger — Possible risk of personal injury or damage to equipment due
to inaccurate or faulty ground cabling.
Inaccurate grounding connection can cause electric shock or equipment
damage when the rack power is switched on.
Note — The grounding cable nuts should be tightened with a torque of
13.28 to 17.7 lbf-in. (1.5 to 2.0 N.m).
STOP. This procedure is complete.