Power Cables; Power Cable Type; Power Cable Routing And Connection - Nokia 7360 Intelligent Services Access Manager FX Series Hardware Installation Manual

Ansi
Hide thumbs Also See for 7360 Intelligent Services Access Manager FX Series:
Table of Contents

Advertisement

7360 ISAM FX-12 shelf cabling
10.5.3
This section provides information about the types of power connection cables, cable
routing, and a procedure for connecting the power cables on the 7360 ISAM FX-12.
10.5.3.1
The 7360 ISAM FX-12 requires the use of an 2 AWG power cable.
10.5.3.2
The power cables are routed through the left side of the rack and can then be routed
to the power distribution terminal block located on the bottom of the shelf; see
Figure 81.
176

Power cables

Power cable type

The color of the power cables must be according to
Note 1 —
local installation practices.
Nokia recommends the following crimp lugs and
Note 2 —
crimp lug tool:
input power lug: 2 AWG, 90C, Burndy YA2CL-2NT14 or
equivalent.
2 AWG 1/4 in. stud with 5/8 in. spacing, dual-hole copper
lug, long barrel, peep, uses Burndy Die Code 10. See
Burndy catalog for additional tool options.
All required washers and nuts are included with the
Note 3 —
shelf.

Power cable routing and connection

3HH-12893-AAAA-TCZZA
ANSI Hardware Installation Manual